Unical ALKON 70 kW Instruction Manual Page 57

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 56
57
Fault finding
Code:
Description: Air in the pump (only for pump with
Sensor Logic
Corrective action: Manually bleed the air from
the circuit
Codice:
Description:
Jammed pump (only for pump with
SensorLogic)
Corrective action:
After removal of the central plug of the pump
body turn with a screw driver the pump rotor
and replace the plug.
Code:
Description:
Failure on the pump wiring (only for pump with
SensorLogic)
Corrective action:
Verify the wiring
Codice:
Description:
Insufficient water circulation
Corrective action:
Verify the installation
which could occur during boiler operation or commissioning
of the boiler.
When the fault signalling led (1) is on, press the LIGHT BLUE
key (2) to check the error code on the display (3).
Description: Failure of the heating return sensor
(SRR)
Corrective action: Check the efficiency of the
sensor and/or wiring
Description: Over high temperature detected by
the heating sensor (SR) (>95°C)
Corrective action: Check the system’s water
circulation
Description: Loss of flame signal during boiler
operation
Corrective action: Press the reset key on the panel
5
FAULT FINDING
2
1
3
5.1 - ERROR CODES
The boiler is fitted with an integrated diagnostic readout which,
in case of malfunction, consents the immediate individuation
of the type of fault directly on the control panel display
In the following fault finding table our purpose is to give some
technical information regarding the solutions to any problems
A
Z
Z
U
R
R
O
V
I
O
L
A
G
I
A
L
L
O
B
L
U
Code:
Description: DHW sensor failure (only if the boiler
is combined with an external storage tank)
Corrective action: Check the sensor’s efficiency
and/or its wiring
Code:
Description: Mains voltage < 190 Vac
Corrective action: Check that the mains voltage
is <190 Vac, if the mains voltage is correct replace
the control board.
Code:
Description: Insufficient gas pressure
Corrective action: Check the pressure; if the
pressure is correct check the efficiency of the gas
pressure switch and/or the wiring.
Code:
Description: Difference between the heating
temperature sensor (SR) and the heating return
sensor (SRR) > 35°C.
Corrective action: Check the installation
Code:
Code:
Code:
Code:
Description: No flame detected during the ignition
phase.
Corrective action: Press the reset key on the
control panel
Page view 56
1 2 ... 52 53 54 55 56 57 58 59 60 61 62 63 64

Comments to this Manuals

No comments