Instructions for the installer
251
71
Smoke evacuation by two separate ducts Ø 80 mm - Type C53
Preliminary operations:
- Fit the supplied pipe of Ø 80 mm, as shown in the picture.
The maximum allowed pressure drop,
independently from the type of installation,
doesn’t have to overcome the value of 60 Pa.
L min = 2 m (1 air intake. + not less than 1 smoke evacuation)
L max = 30 m (15 air intake. + 15 smoke evacuation)
KIT5780C
KIT5770C
TSC0130C
TSC0130C