Instructions for the installer
Preliminary operations:
- Insert the supplied pipe Ø 80 in the adapter for coaxial
pipes Ø80/125 (code 00361255)
- Fit the assembly pipe/adapter on the boiler as shown in
figure.
HORIZONTAL FLUE OUTLET WITH CONCENTRIC DUCTS Ø 80/125 mm - Type C 13
L min = 1 m - L max = 5 m
00361256
00361255
00360357
The minimum allowed length of the horizontal
coaxial pipes is 1 meter.
The maximum allowed length of the horizontal
coaxial pipes is 5 meters.
For every additional curve the maximum allowed
length must be reduced by 1 meter; besides the
duct has to have an upward inclination of 3% in
the direction of exit, so that to allow the collection
of the condensate in to the boiler.