Technical features and dimensions
2.1 - TECHNICAL FEATURES
The ALKON 50/70 boilers are a thermals gas fired units with
an atmospheric fully pre-mixed burner.
They are supplied only in heating version.
These boilers have an input head power of: 50 or 70 kW,
These boilers are designed for use on gas category II2H3P.
The ALKON boilers are supplied complete with all the safety
and control devices in accordance with all the current
regulations and the following European directives:
– Gas Directive 90/396 CEE
– Efficiency Directive 92/42 CEE
– Electromagnetic Compatibility Directive 2004/108 CEE
– Low Voltage Directive 2006/95 CEE.
Moreover, the boilers of the ALKON range are classified as
“CONDENSING BOILERS” according to the Directive 92/42
CEE appendix 2 (4 stars).
DESCRIPTION OF COMPONENTS AND FEATURES
:
Aluminium heat exchanger/condenser;
Fully premixed burner working at constant CO2;
Electronic ignition;
Safety high limit thermostat;
Flow temperature sensor;
Return temperature sensor;
2
615
930
266
85 110 110 132 100 78
78
430 107
125
179
RMG
Sc
Scf
R CH system return 1’’ (1 ¼’’ for 70 kW)
M CH flow system 1’’ (1 ¼’’ for 70 kW)
G Gas Inlet Ø ¾’’
Sc Outlet condensate drain siphon (corpo alluminio)
SV
135
180
78
266
A
S
Scf Outlet condensate drain siphon (proveniente dal tubo scarico fumi)
SV Safety valve outlet
A Air intake
S Flue Outlet
TECHNICAL FEATURES
AND DIMENSIONS
2.2 - DIMENSIONS
Automatic air vent;
Drain condensate siphon
Control panel with electrical protection IP X4D;
eBUS device;
CH temperature selector switch: 30 ÷ 85°C;
Flame modulation in function of the absorbed power;
Pump overrun function;
Additional functions : diagnostics of operation parameters
and troubles, antifreeze, technical functions and digital in-
dication of failures.
Constant combustion ratio
Self adapting output depending on the length of flue ducts
Modulating pump for ALKON 70
OPTIONAL KITS:
Kit of manidold for additional safety devices
Kit of additional safety devices
Krömschröder controller E8/Expansion modules and
modulating thermostats
(case for wall mounting)
Kit of boiler pump (at constant or modulating flow rate:
only for ALKON 50)
Mixing bottle Kit
Chimney for single, battery or cascade mounting
Supporting frames
Kit for D.H.W. priority
Kit of blind flanges and hydraulic manifolds
Kit of wiring harness for external D.H.W. tank
VIEW FROM ABOVE
VIEW FROM BELOW