Page 1 - ALKON 50 kW

00333009/a - 3rd edition - 02/10ALKON 70 kWALKON 50 kWINSTALLATIONAND SERVICINGMANUALENGLISH

Page 2

10Technical features and dimensions2.3 - MAIN COMPONENTSN.B.:The boiler cannot work on natural circulationALUMINIUM HEATEXCHANGER/CONDENSERCONDENSATED

Page 3 - GENERAL INFORMATION

11Technical features and dimensionsALKON 70ALUMINIUM HEATEXCHANGER/CONDENSERCONDENSATEDRAIN (Ø25 mm)AIRVENTVALVEMODULATINGFANAIR INTAKEOPENING (Ø80 mm

Page 4 - General Information

12Technical features and dimensionsMRG123456781291011131415ATTENTION!THE PRE-FORMING FOR THE BOILER PUMP ISONLY FOR THE PUMP KIT SUPPLIED BYUNICAL0036

Page 5

13Technical features and dimensions2.6 - GENERAL FEATURES2.5 - PERFORMANCE DATAl/minbarbarmbarl°C°Clbarllbarbarl/min.l/min.l/min.l/min.l/min.l/min.l

Page 6

14Instructions for the installer3INSTRUCTIONS FORTHE INSTALLER3.1 - GENERAL WARNINGSWARNING!This boiler has to be destined for the use forwhich it has

Page 7 - AND DIMENSIONS

15Instructions for the installer3.2 - STANDARD CODES FORINSTALLATIONThe appliance must be installed in compliance to theinstructions contained in thi

Page 8

16Instructions for the installer3707151025Special attention shall be paid to local regulations and lawsabout boiler houses and particularly to the obl

Page 9

17Instructions for the installer- The boiler room has a suitable outlet for the discharge ofcondensate produce by the boiler.- The electrical system h

Page 10 - ALKON 50

18Instructions for the installer3.7 - FLOW AND RETURN PIPE CONNEC-TIONSThe CH flow and return circuits have to be connected to theboiler via the resp

Page 11 - ALKON 70

19Instructions for the installerThe size of the pumps must be determinedby installers or technical engineersaccording to boiler data and systemdesign.

Page 12

2CONTENTS1 GENERAL INFORMATION ...

Page 13 - 2.5 - PERFORMANCE DATA

20Instructions for the installerFor the electrical connection of theadditional safety devices make referenceto the paragraph 3.17 - Connection of thea

Page 14 - THE INSTALLER

21Instructions for the installer3.11 - WORKING PRESSUREThe boiler’s maximum allowable working pressure is set at3 bar; whilst the minimum pressure is

Page 15 - INSTALLATION

22Instructions for the installerIn order to ensure correct boiler operation it is necessary touse a mixing header which guarantees:- the separation an

Page 16 - 3.3 - PACKAGING

23Instructions for the installerABC3.14 - CONDENSATE DRAINDuring the combustion process the boiler producescondensate which, through the “A” pipe, flo

Page 17 - 3.6 - GAS CONNECTION

24Instructions for the installer3.15 - WATER TREATMENTThe chemical/physical features of the heating system’s waterare fundamental for the boiler’s c

Page 18 - 1” or 1’’¼ as indicated

25Instructions for the installer3.16 - FLUE OUTLET INSTALLATIONThe flue system must be installed in accordance with thelocal and national Standards.

Page 19 - Pressure losses (mmH2O)

26Instructions for the installer L min = 1 m - L max = 30 mKIT5790CKIT5750C - KIT5760C (1 m) - (0,5 m)TSC0130C00310012Preliminary operation

Page 20

27Instructions for the installerPreliminary operations:- Insert the supplied pipe Ø 80 in the adapter for coaxialpipes Ø80/125 (code 00361255)- Fit th

Page 21 - 3.11 - WORKING PRESSURE

28Instructions for the installer L min = 1 m - L max = 7 mKIT5820CKIT5730C(1 m)00361255Preliminary operations:- Insert the supplied pipe Ø 80 in the

Page 22 - 3.13 - MIXING HEADER

29Instructions for the installer25171Smoke evacuation by two separate ducts Ø 80 mm - Type C53Preliminary operations:- Fit the supplied pipe of Ø 80

Page 23 - 3.14 - CONDENSATE DRAIN

3General Information1.1 - SYMBOLS USED IN THIS GUIDEWhen reading this guide particular care has to be given to the parts marked with the followings sy

Page 24 - 1 2 3 4 5 2 7 16

30Instructions for the installer3.17 - ELECTRICAL CONNECTIONSRegulations in forceThe elctrical safety of the appliance is assured only when it iscorre

Page 25

31Instructions for the installerConnection of the additional safety devices- Gain access to the Y1 terminal board- A Room Thermostat will be connected

Page 26 - L min = 1 m - L max = 30 m

32Instructions for the installerDANGER!Switch off and disconnect the electricitysupply before carrying out any operations onthe electrical parts.- Fo

Page 27 - 00360357

33Instructions for the installer3.18 - ACTUAL WIRING DIAGRAM for ALKON 50E. ACC = Ignition electrodeE. RIV. = Detection electrodeDK = Minimum water pr

Page 28 - KIT5730C

34Instructions for the installerACTUAL WIRING DIAGRAM for ALKON 7021VMORANGE +BLACK (-)BROWN (PWM)BLUE (TACHO)45LIGHT-BLUE (N)12BROWN (L1)3RIL./REG.AL

Page 29 - Preliminary operations:

35Instructions for the installerBoiler pump at constant flow rate (optional cod. 00361321 ALKON 50)Modulating pump (optional cod. 00361320 ALKON 50)P

Page 30 - Regulations in force

36Instructions for the installer3.19 - WIRING DIAGRAM AND MANAGEMENT WITH E8 REGULATOR (Optional)12345678910IIA1 A2 A3 A4 A5 A6NL1L1’MT1 T212A7T3 T4VI

Page 31 - E8 heating

37Instructions for the installerSensor terminal assignmentsConnection to BCMFor connection to remote control devicesTerminal VIIVIIeBUSFA0-10 V12VIIP

Page 32 - Attention

38Instructions for the installerVF1VFVFAFM R G < 1 mFilter Expansionvessel(optional)Safety devices kitMixing HeaderHeating Circuit 1OutsideSensorNO

Page 33

39Instructions for the installerF Ric. C VFVFSPF12n4VFVFVFAFM R G < 1 mFilter Heating Circuit 1Heating Circuit 2Mixing HeaderSafety devices kitExp

Page 34 - Prearrangement for the

4General InformationWARNING!The installation, adjustment, and servicing of this appliance must be carried out by a competent person andinstalled in ac

Page 35 - YELL-GREEN

40Instructions for the installerF Ric. C VFVFSPF21n4VFVFVFAFM R G < 1 mFilter Heating Circuit 1Heating Circuit 2Mixing HeaderSafety devices kitExp

Page 36 - :

41Instructions for the installerF Ric. C VF VFSPF12n4VFVFVFAFSonda dicaldaiaM R G < 1 mFilter Heating Circuit 1Heating Circuit 2Mixing HeaderSafet

Page 37 - Sensor terminal assignments

42Instructions for the installerC VFVFSPF12VFVFVFF A1154PT10002+F14F122+AFM R G < 1 mFilter Heating Circuit 1Heating Circuit 2Mixing HeaderSafety

Page 38

43Instructions for the installerF Ric. C VFVFSPF12n4VFVFVFAFM R G M R G < 1 mKFBoiler sensorFilter Heating Circuit 1Heating Circuit 2Mixing Header

Page 39

44Instructions for the installer1 - 00361366 = Supporting frame for one boiler2 - 00361314 = Manifold kit for Alkon 50/703 - 00361313 = Pipe kit for a

Page 40

45Instructions for the installer1 - 00361363 = Supporting frame for two boilers2 - 00361314 = Manifold kit for Alkon 50/703 - 00361313 = Pipe kit for

Page 41

46Instructions for the installer1 - 00361363 = Supporting frame for two boilers1a - 00361365 = Added supporting frame for one boiler2 - 00361314 = Man

Page 42 - < 1 m

47Instructions for the installer1 - 00361363 = Supporting frame for two boilers1a - 00361365 = Added supporting frame for one boiler2 - 00361314 = Man

Page 43 - Input of the basic

48Instructions for the installer3.22 - FILLING THE SYSTEMWarning!Do not mix the CH system’s water with anti-freeze or anti-corrosion solutions using

Page 44

49Instructions for the installer3.23 - INITIAL LIGHTINGPRELIMIARY CHECKSThe first ignition must be carried out by aqualified technician. Failure to do

Page 45

5General InformationLEGEND:1 = CE Surveillance notify body2=Boiler type3=Boiler model4=Number of stars (Directive 92/42/CEE)5=(S.N°) Serial number6=P.

Page 46

50Instructions for the installer11VIOLAGIALLOAZZURROBLUVIOLAGIALLOAZZURROBLUVIOLAGIALLOAZZURROBLU13.24 - BURNER ADJUSTMENTWARNING!All the instruction

Page 47

51Instructions for the installerALKON 5020371,02 m³/h0,75 kg/h5,13 m³/h3,76 kg/h48,5-9,648,5-9,6--9,511,0959226245,65,6--9,511,04045FL e FH = paramet

Page 48 - 3.22 - FILLING THE SYSTEM

52Instructions for the installerThe boilers are specifically produced for the type of gasrequested at the ordination phase.DANGER!The transformation o

Page 49 - 3.23 - INITIAL LIGHTING

53Instructions for the installer3.27 - PROGRAMMING OF THE OPERATING PARAMETERSWARNING! THESE OPERATIONS ARE ACCESSIBLE TO TRAINED INSTALLERS AND SERVI

Page 50 - 3.24 - BURNER ADJUSTMENT

54Instructions for the installerMODULATING PUMP MINIMUM MODULATION LEVELContinue to change to the parameters by pressing the – key(decrease).The succ

Page 51 - INJECTORS – PRESSURES

55Servicing scheduleRelationship between the temperature (°C) and the nominalresistance (Ohm) of the CH sensor and the DHW sensors.T°C01234567890 3275

Page 52

56Servicing scheduleCLEANING THE CONDENSATE DRAINSIPHON134SEALING GASKET BETWEEN DISTRIBUTORAND BOILER BODYDANGER!It is absolutely necessary to replac

Page 53 - PUMP OVERRUN

57Fault findingCode:Description: Air in the pump (only for pump withSensor LogicCorrective action: Manually bleed the air fromthe circuitCodice:Descri

Page 54

58Fault findingThe boiler has an integrated system that, after 10.000switching On or 2.000 hours of operation of the burner,provides to signal that th

Page 55 - Servicing schedule

59Fault findingCode:Description:Air in the pump (only for pump with SensorLogicCorrective action:Manually bleed the air from the circuitCode:Descripti

Page 56

6General Information1.7 - GENERAL WARNINGSThis instruction manual is an integral and indispensablepart of the product and must be retained by the pers

Page 57 - FAULT FINDING

60Fault findingCode:Description:Lack of water (only for pump with SensorLogic)Corrective action:Fill the hydraulic circuitCode:Code:Description:Flame

Page 58 - Fault finding

61PIN n° 1312BQ4306Nota: E’ possibile che alcuni prodotti descritti, non siano commercializzati.Note: It is possible that some of the product indica

Page 61 - DECLARATION OF CONFORMITY

AG S.P.A.46033 casteldario - mantova - italia - tel. 0376/57001 (r.a.) - fax 0376/660556www.unical.ag - [email protected] Unical declines every

Page 62

7Technical features and dimensions2.1 - TECHNICAL FEATURESThe ALKON 50/70 boilers are a thermals gas fired units withan atmospheric fully pre-mixed

Page 63

8Technical features and dimensions1510502762197871230405001500243119721740DIMENSIONS ALKON 50/70 + KIT SAFETY DEVICES + HYDRAULIC HEADER +Y FILTER KIT

Page 64 - AG S.P.A

9Technical features and dimensions2475197250015001740372625101972500150017404630DIMENSIONS ALKON 50/70 in BATTERY (n.3 boilers) + KIT SAFETY DEVICES